Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/11/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
12/29/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Comment not addressed. This activity is being reviewed to the 2006 UPC. If the 2006 IPC is desired, submit an appeal to the building official. 2. Comment not addressed. The minimum residual water pressure is 15 PSI, not 8 PSI. Reference: Section 608.1, UPC 2006. 3. Comment not addressed. Provide an upper terminal cleanout for the break room sink. Reference: Section 707.4, UPC 2006. |
12/29/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Revise the size of the condensate drains in accordance with Section 307.2.1, IMC 2006, as amended by the City of Tucson (i.e. combining 2 units of any size requires a minimum 1" condensate drain). |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
01/12/2010 | SUE REEVES | OUT TO CUSTOMER | Completed |
01/12/2010 | SUE REEVES | REJECT SHELF | Completed |