Review Details: COMMERCIAL TI

Permit Number - T09CM00207
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/28/2009 MICHAEL ST. PAUL ZONING REVIEW Approved
01/28/2009 GERRY KOZIOL WWM REVIEW Approved
12/10/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
12/10/2009 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Approved
12/10/2009 ERIC NEWCOMB ZONING HC REVIEW Approved
12/11/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Needs Review
12/11/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. This activity is being reviewed to the 2006 UPC. If the 2006 IPC is desired, submit an appeal to the building official.
2. The minimum residual water pressure is 15 PSI, not 8 PSI. Reference: Section 608.1, UPC 2006.3. Provide an upper terminal cleanout for the breakroom sink. Reference: Section 707.4, UPC 2006.
3. Appliances (e.g. ice makers) to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps conforming to Table 6-3, UPC 2006 require backflow prevention. Reference: Sections 602.3, 603.0, and Table 6-2, UPC 2006.
4. Clarify the need for drainage for the ice machine. Reference: Sections 103.2.3 and 801.2, UPC 2006.
12/11/2009 ROBERT SHERRY WATER REVIEW Approved
12/14/2009 DROBEY1 ELECTRICAL-COMMERCIAL REVIEW Needs Review