Permit Number: T09CM00186
Parcel: 12616319D

Review Status: Active

Review Details: OTHER

Permit Number - T09CM00186
Review Name: OTHER
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
01/27/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved Project:445 S Alvernon ,Gem Show Tent Service
T09CM0186

Will require the following information in order to issue permit:

1. Give the following information on the generators, voltage,amperage.
2. Provide a diagram of the grounding systems for each showing two ground rods and the conductor size to be used for the grounded conductor electrode.
3.You have given the size of the cable to be used to feed the stringer boxes, what type of cable will this be ? Will the cable be on ground ?
4. What will be the overcurrent prtection size on the generator for each cable ?
5. Will the stringer boxes have over-current protection on them ? What size ?


Ray T Majuta, DSD City of Tucson,
Elect Plan Ck, 1-27-09