Permit Number: T09CM00133
Parcel: 11615088L

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T09CM00133
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/21/2009 ROBERT SHERRY ZONING HC SITE REVIEW Approved
01/21/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied CLARIFY THE DOOR GRILLES; THE MODEL NUMBERS ARE BY RUEGER, NOT RUSKIN.
01/21/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
01/21/2009 DAVE MANN FIRE REVIEW Approved
01/21/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. ROOMS 1702 AND 1703A MUST HAVE 1 HOUR FIRE RATED WALLS, FIRE RATED DOORS/OPENINGS, AND A 1 HOUR FIRE RATED FLOOR/CEILING ASSEMBLY ABOVE THESE ROOMS. SHOW THESE ASSEMBLIES ON THE PLANS.
01/21/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
01/21/2009 ROBERT SHERRY ADA REVIEW Passed
01/29/2009 CPIERCE1 ENGINEERING REVIEW Needs Review
01/29/2009 CPIERCE1 ZONING REVIEW Needs Review
01/29/2009 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review