Permit Number: T09CM00103
Parcel: 11006014P

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T09CM00103
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/15/2009 TERRY STEVENS ZONING REVIEW Approved
01/15/2009 BIANCA RAMIREZ ENGINEERING REVIEW Approved
01/15/2009 RONALD BROWN ZONING HC SITE REVIEW Approved
01/15/2009 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
01/15/2009 RONALD BROWN ADA REVIEW Passed
01/16/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
01/16/2009 MARTIN BROWN FIRE REVIEW Approved
01/16/2009 ROBERT SHERRY WATER REVIEW Approved
01/16/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied PROJECT; 3988 E FORT LOWELL RD
T08CM00103
OFFICE TI

THE FOLLOWING ITEMS NEED TO BE ADDRESSED;
1. THE SERVICE IS REQUIRED TO BE TIED TO REBAR FIRST, AND IF WATER IS METALLIC INDICATE A BOND.
2.THE CALCULATIONS ARE DONE IN A RESIDENTIAL MANNER, PLEASE REDO IN A COMMERCIAL MANNER, THE WATTS PER SQUARE FOOTAGE FOR OFFICE TYPE BUILDING IS 3.5 NOT 2 WATTS.
3. COMMERCIAL T I'S REQUIRE A LIGHTING ALLOWANCE CALCULATION PER THE 2006 IECC CODE TO BE SUBMITTED WITH PLANS.
4. YOU ARE REQUIRED TP PROVIDE A LIGH SCHEDULE SHOWING FIXTURE INFORMATION, SUCH AS WATTAGE USED, VOLTAGE. AND FOR OUTSIDE FIXTURES INFORMATION ON IF CUT-OFF TYPE AS REQUIRED BY THE OUT-DOOR LIGHTING CODE--ORD #10135.


RAY T MAJUTA
ELECTRICAL PLAN CHECK
CITY OF TUCSON DSD
520-837-4988
1/16/09
01/16/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
01/20/2009 GERRY KOZIOL WWM REVIEW Approved
01/20/2009 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed