Permit Number: T09CM00096
Parcel: 128100560

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T09CM00096
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/14/2009 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
01/20/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
01/20/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T09CM00096
310 S Williams Blvd

Project has failed for the following:
1. New panel shows a 200 amp feeder , connected to a 100 amp cb, and to a 100 amp panel.

Ray T Majuta
DSD City of Tucson
1/20/09
01/20/2009 ROBERT SHERRY WATER REVIEW Approved
01/20/2009 MICHAEL ST. PAUL ZONING REVIEW Approved
01/20/2009 RSHERRY1 WWM REVIEW Passed No new plumbing fixtures
01/20/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
01/20/2009 JASON GREEN ENGINEERING REVIEW Approved
01/20/2009 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
01/20/2009 RONALD BROWN ZONING HC SITE REVIEW Approved
01/20/2009 DAVE MANN FIRE REVIEW Approved
01/20/2009 RONALD BROWN ADA REVIEW Passed