Permit Number - T09CM00057
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/23/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide an expansion tank for the water heater. 2. Show the location of the water heater in the building and the piping configuration. |
| 01/23/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Show how the solar collecter system is to be protected from excess temperatures 9e.g. the maximum temperature for the specified expansion tank is less than the maximum system pressure). 2. Confirm the sizing of the expansion tank. |