Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T09CM00050
Parcel: 133553310

Address:
250 S VOZACK LN

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T09CM00050
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/14/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET T1.0; CODE ANALYSIS DATA: REVIEW OCCUPANCY GROUP (R-4) AND OCCUPANT LOAD (30). GROUP I-1 FOR HOUSING OF MORE THAN 10 PERSONS MIGHT BE MORE SUITABLE. 200 SF/OCCUPANT IS ACCEPTABLE FOR RESIDENTIAL OR KITCHEN OCCUPANCY, BUT NOT FOR THE 5963 SF BUILDING (SEE IBC TABLE 1004.1.1).
2. SHEET A2.1; SECTIONS 1/2/3: INDICATE ON THE SECTIONS HOW THE NEW HEADER OVER THE OPENING IS CONNECTED TO THE JAMB FRAMING AT EACH END.
3. SHEET A2.1; KITCHEN PLAN: REVISE DETAIL DESIGNATION FROM 3/4 TO 4/A2.1. CHANGE DETAIL NUMBER. VERIFY.
01/14/2009 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
01/14/2009 ERIC NEWCOMB ZONING HC SITE REVIEW Denied 1. SEE BUILDING COMMENTS.
01/28/2009 GERRY KOZIOL WWM REVIEW Approved
02/02/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide information regarding the flue for the new water heater; no information is shown on the mechanical drawings. Reference: Section 103.2.3, UPC 2006.
2. Provide a floor drain in the kitchen scullery area. Reference: Sections 411.2.2 and 704.3, UPC 2006.
3. Clarify the location of P-1 in the scullery area; if the indirect waste pipes to it are longer than 5'-0", the trap requirements of Section 803, UPC 2006 will be applicable.
4. The waste and vent isometric calls for the hydromechanical grease interceptor to be located above ground but its protecting vent starts below ground; clarify how this is possible. In addition, if the waste piping is made of PVC or ABS rather than cast iron, it shall not be exposed to sunlight and shall be protected from freezing. Reference: Sections 103.2.3, 701.1, IS-5 and IS-9, UPC 2006.
02/02/2009 ROBERT SHERRY WATER REVIEW Approved
02/02/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Coordinate the balancing information for the make up air to the Type I hood; the plans call for 1,000 CFM to the make up air plenum but the hood manufacturer limits the air delivered to the plenum to a maximum of 990 CFM. Reference: Section 304.1, IMC 2006.
2. Clarify the requirement for selecting the exhaust fan for an elevation of 8,000 feet. Reference: Section 106.3.1, IMC 2006.
02/06/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
02/10/2009 CINDY AGUILAR OUT TO CUSTOMER Completed
02/10/2009 SUE REEVES REJECT SHELF Completed