Review Details: RESIDENTIAL BLDG/ZONING/ENGINE/WWM

Permit Number - T09CM00029
Review Name: RESIDENTIAL BLDG/ZONING/ENGINE/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/08/2009 GERRY KOZIOL WWM REVIEW Approved
01/14/2009 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS
Date: 1-16-09
Activity: T09CM00029
Address: 1240 E. Allen Rd.
Applicant: Rick Merfeld

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review includes architectural, electrical, plumbing, mechanical, and energy conservation. The purpose of this review is to verify compliance to the 2006 International Residential Code with local amendments. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

GENERAL REQUIREMENTS:
1. Provide two copies of the corrected set of drawings (no clouds or revision numbers please) along with a set of the first submission (cloud corrections on this set please). All corrections and revisions shall be made on original tracings or finished reproducible set. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets.
2. Any architect and/or engineer involved in the design of the structure shall seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

FLOOR PLANS:
3. Ref: Master Bathroom. Specify safety glazing in hazardous locations (within 24" of doorways) R308.4.

PLUMBING PLAN:
4. Provide a gas line isometric and size the supply pipe for the connected demand. Include the length of line and BTU demand for each appliance, size of each branch, total demand, and total developed length from meter to the most remote appliance on the system, G2413.1, Table G2413.4 (1).
5. Provide note requiring that water hammer arrestor be installed in accordance with ASSE 1010-2004 on water lines serving appliances equipped with quick-closing valves to include but not limited to: clothes washers, dishwashers, and refrigerators, IRC P2903.5.
6. Provide a water fixture unit schedule for the entire property (including existing) P2903.6.
7. Specify the maximum developed length of water line from the meter the furthest appliance served, the meter size, available pressure, and the diameter of the water service line, P2903.7.

MECHANICAL PLAN:
8. Specify a minimum of two (2) 100 square inch openings for combustion air requirements, M1702.2.

ELECTRICAL PLAN:
9. Ref: Master Bedroom. Show receptacle outlets at wall spaces 2' or more so that no point along the wall (excluding door openings) is more than 6' from a receptacle outlet, E3801.2.

If you have any questions please contact:
Clayton Trevillyan
520.837.4913
Residential Plan Review