Permit Number: T09BU01907
Parcel: 13409018B

Review Status: Completed

Review Details: RESUBMITTAL - GRADING ALL

Permit Number - T09BU01907
Review Name: RESUBMITTAL - GRADING ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/16/2010 ANDREW CONNOR NPPO REVIEW Denied The grading plan has been reviewed by the Landscape / NPPO Section but cannot approve the plan until all Engineering, comments, concerns, and appropriate revisions have been addressed.
03/17/2010 ANDREW CONNOR ZONING REVIEW Denied The grading plan has been reviewed by the Zoning Section but cannot approve the plan until all Engineering, comments, concerns, and appropriate revisions have been addressed.
03/26/2010 JASON GREEN ENGINEERING REVIEW Denied DATE: March 30, 2010
SUBJECT: 8578 E Broadway Blvd Site and Grading Plan- 2nd Engineering Review
TO: MPE Attn: Lisa Bowers
LOCATION: T14S R15E Sec16 Ward 2
REVIEWERS: Jason Green, CFM
ACTIVITY: T09CM03408 (Site Plan), T09BU01907 (Grading Plan)


SUMMARY: Engineering Division of Planning and Development Services Department has received and reviewed the revised site plan (T09CM03408), Grading Plan (T09BU01907), Drainage Statement (Stanley Engineering & Drainage, Inc., 22DEC09), and Geotechnical Engineering Report (Terracon, 11NOV09) for the above referenced property. Engineering Division does not recommend approval of the plan sets at this time. The following items need to be addressed:


SITE PLAN COMMENTS:

1) Complied.

2) Complied.

3) Complied.

4) Acknowledged.

5) Complied.

6) Complied.

7) Complied.

8) Complied.

9) The seal on the Site Plan must be signed and dated by the Registered Architect of Record that prepared the plan set. None of the signed seals had the date of signature.


GRADING PLAN COMMENTS:

10) Restated: Provide a copy of the stamped approved site plan (T09CM03408). The grading plan can not be approved until verification that all details, locations, dimensions, and plan profiles match the approved site plan. Verify all information associated with the site plan is shown on the grading plan which will be used as the construction document.

11) Complied.

12) Complied.

13) Complied.

14) Complied.

15) Complied.

16) Complied.

17) Complied.

18) Complied.

19) Complied.

20) Complied.

21) Complied.

22) Complied.

23) Complied.

24) Complied.

25) Complied.


GENERAL COMMENTS:

Please provide a signed and dated site plan from the Architect of Record and the proposed grading plan that addresses the comments provided above. Include a comprehensive response letter addressing in detail responses to all of the above comments.

For questions or to schedule an appointment I can be reached at 837-4929.



Jason Green, CFM
Senior Engineer Associate
Engineering Division
COT Planning & Development Services

Final Status

Task End Date Reviewer's Name Type of Review Description
04/07/2010 DELMA ROBEY OUT TO CUSTOMER Completed
04/07/2010 SUE REEVES REJECT SHELF Completed