Permit Review Detail
Review Status: Completed
Review Details: POOL:COMM-MODEL
Permit Number - T09BU01884
Review Name: POOL:COMM-MODEL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/04/2010 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 01/05/2010 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 01/05/2010 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 01/05/2010 | PAUL MACHADO | ENGINEERING | REVIEW | Approved | |
| 01/05/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide plans sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304. 2. Specify the schedule of the PVC pipe to be used for the pool circulation system. 3. Provide a SVRS for the pool. 4. Confirm the velocity of the water in the suction and return piping, based on a 60 GPM circulation rate. |
| 01/05/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Project: 801 W Miracle Mile, T09BU01884 Pool The electrical plans have been denied for the following: 1. Provide location on plan for Panel HPE,( pnl feeding the pool panel). 2. Show size conductors and conduit feeding pool panel from panel HPE. 3. The pool panel is in an independent structure, it must have it's own grounding system,provide one on plan. Ray T Majuta Elect Pln Ck,PDSD, City of Tucson 1/05/10 Ray.Majuta@tucsonaz.gov |