Permit Review Detail
Review Status: Completed
Review Details: GRADING
Permit Number - T09BU01880
Review Name: GRADING
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/04/2010 | DAVID RIVERA | ZONING | REVIEW | Approved | |
| 01/07/2010 | ANDREW CONNOR | NPPO | REVIEW | Completed | Ensure that all Engineering comments and concerns are addressed prior to NPP/Landscape approval. |
| 01/08/2010 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | The sidewalk must be vertically separated from the gravel drive where they abut. |
| 01/11/2010 | RONALD BROWN | ZONING HC | REVIEW | Denied | 1. Please provide an accessible passenger loading zone as per ICC (ANSI) 117.1, Section 503. 2. As per 2006 IBC, Section 1108.2 Assembly Area Seating and ICC (ANSI) Section 802, please provide required accessible wheel chair seating area identified with the international accessible symbol with an adjacent companion regular seating also identified with the international accessible symbol. 3. Insure that all accessible route slopes adhere to ICC (ANSI) Section 403.3. END OF REVIEW |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/11/2010 | GERARDO BONILLA | OUT TO CUSTOMER | Completed |
| 01/11/2010 | SUE REEVES | REJECT SHELF | Completed |