Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T09BU01793
Parcel: 11519002J

Address:
1425 W GRANT RD

Review Status: Completed

Review Details: TANKS

Permit Number - T09BU01793
Review Name: TANKS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/31/2010 MARTIN BROWN FIRE REVIEW Approved