Permit Number: T09BU01793
Parcel: 11519002J

Address:
1425 W GRANT RD

Review Status: Completed

Review Details: TANKS

Permit Number - T09BU01793
Review Name: TANKS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/04/2010 STEVE SHIELDS ZONING REVIEW Approved
12/16/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
12/18/2009 DAVE MANN FIRE REVIEW Denied Dispenser islands must be 6 inches high or multiple bollards must be 3 feet tall. The site plans conflict with the tank plans allowing 2' 6 " bollards. See Sheets GG-01 and GC04.1. See IFC 312.

Final Status

Task End Date Reviewer's Name Type of Review Description
02/01/2010 CPIERCE1 OUT TO CUSTOMER Completed
02/01/2010 SUE REEVES REJECT SHELF Completed