Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: TANKS
Permit Number - T09BU01793
Review Name: TANKS
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/04/2010 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 12/16/2009 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 12/18/2009 | DAVE MANN | FIRE | REVIEW | Denied | Dispenser islands must be 6 inches high or multiple bollards must be 3 feet tall. The site plans conflict with the tank plans allowing 2' 6 " bollards. See Sheets GG-01 and GC04.1. See IFC 312. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/01/2010 | CPIERCE1 | OUT TO CUSTOMER | Completed |
| 02/01/2010 | SUE REEVES | REJECT SHELF | Completed |