Permit Number: T09BU01778
Parcel: 12218232A

Review Status: Completed

Review Details: RESUBMITTAL - GRADING ALL

Permit Number - T09BU01778
Review Name: RESUBMITTAL - GRADING ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/04/2010 JASON GREEN ENGINEERING REVIEW Denied DATE: March 4, 2010
SUBJECT: 3607 E Speedway Blvd- 2nd Engineering Review Site and Grading Plan
TO: SCE Corporation Attn: Charles Corrales
LOCATION: T14S R14E Sec04 Ward 6
REVIEWERS: Jason Green, CFM
ACTIVITY: T09CM03157 (Site Plan), T09BU01778 (Grading Plan) and T10OT00094 (Floodplain Use Permit)


SUMMARY: Engineering Division of Planning and Development Services Department has received and reviewed the revised site plan (T09CM03157), grading plan (T09BU01778), Floodplain Use Permit (T10OT00094) and Drainage Report (SCE Corporation, 07DEC09) for the above referenced property. Engineering Division does not recommend approval of the site plan or grading plan at this time. The following items need to be addressed:

NEW COMMENT:

" Remove the Architect Seal from the plan since the plan was prepared, sealed and signed by the civil engineer. Or provide the signature and date of the Registered Architect on all sheets.

SITE PLAN COMMENTS:

1) Acknowledged.

2) Restated: Revise the site plan sheet to provide the correct activity numbers assigned to this project. The reference to the FUP should read "T10OT00094" not T0DT00094.

3) Completed.

4) Completed.

5) Completed.

6) Restated; DS Sec.2-02.2.1.A.8: Provide a cross access and cross parking agreement between the existing 2 lots. Or provide a lot combination approval through the Zoning Section.

7) Restated: DS Sec.2-02.2.1.A.8: Revise the plan set to label the minimum 24-foot PAAL widths at all PAAL intersections, property lines and adjacent to both proposed refuse container locations. This was not fully addressed at the refuse locations. A minimum 24-foot clear PAAL width must be labeled even when the refuse container door is open.

8) Acknowledged. Gates to remain open during business hours.

9) Completed.

10) Completed.

11) Completed.

12) Completed.

13) Restated: DS Sec.2-02.2.1.A.12: Provide a minimum 3-foot wide gate at the sidewalk location west of Bay 1. Per the plan set the proposed chain link fence crosses the sidewalk and does not label a pedestrian access gate, revise. Refer to comments from Ron Brown, RA Structural Plans Examiner for all onsite handicap and ANSI Standard requirements that apply to this project.

14) Acknowledged. The redline comment did not apply to the loading zone. However it has been noted that the proposed loading zone has been removed from the project.

15) Completed.

16) Restated: DS Sec.2-02.2.1.A.19: Revise the plan sheets to label both Richey Blvd and Speedway Blvd as "Public."

17) Restated: DS Sec.2-02.2.1.A.32: Revise the plan set and detail for the proposed refuse container that meets the minimum requirements within DS Sec.6-01. Revise the detail to clearly label the minimum 5-inch thickness for the concrete slab.

18) Restated: DS Sec.2-02.2.1.A.32: Provide written approval from Environmental Services for refuse maneuverability. Provide the required 14-foot by 40-foot clear approach and verify the maximum allowed back up distance for maneuverability. Refuse vehicles can not back up into required parking spaces.

19) Be advised that further comments may be forth coming on resubmittal of the site plan and grading plan.


GRADING PLAN:

20) Acknowledged.

21) Completed.

22) Completed.

23) Completed.

24) Restated: Provide a General Grading/Paving Note on the plan set to state all of the following, "Call for a Pre-construction meeting prior to start of earthwork. To schedule a PDSD Pre-construction meeting, SWPPP inspection or general Engineering Inspections, call IVR (740-6970), or schedule with a Customer Service Representative at the Planning Development Services Department, or contact PDSD Engineering at 791-5550 extension 2101, or schedule inspections online at:
http://www.ci.tucson.az.us/dsd/Online_Services/Online_Permits/online_permits.html"


FLOODPLAIN USE PERMIT:

25) Restated: A Floodplain Use Permit (T10OT00094) was submitted for this project due to the improvements within the mapped 100-year floodplain per the referenced Drainage Report. The Floodplain Use Permit will be approved and conditioned based upon grading plan approval.


GENERAL COMMENTS:

Please provide a revised site plan and grading plan set that addresses the comments provided above. Include a comprehensive response letter addressing in detail responses to all of the above comments. Enclose "redlines" with the resubmittal package.

Further comments may be generated upon resubmittal of the plan review.

A meeting is requested for this project prior to resubmittal to help ensure a timely review, call me at 837-4929.



Jason Green, CFM
Senior Engineer Associate
Engineering Division
COT Planning & Development Services
03/04/2010 STEVE SHIELDS ZONING REVIEW Denied PDSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: DSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: James Autosports
T09BU01778
Grading Plan (2nd Review)

TRANSMITTAL DATE: January 25, 2010

1. The grading plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. Zoning could not verify that the grading plan was in compliance with the approved site plan. Please submit two copies of the approved and stamped site plan with the next grading plan submittal.

3. Zoning will re-review the grading plan on the next submittal to insure compliance with the approved and stamped site plan. Additional comments may be forthcoming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956

C:\planning\grading\t09bu01778

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Approved site plans and additional requested documents
03/08/2010 ANDREW CONNOR NPPO REVIEW Denied Ensure that all Engineering comments and concerns are addressed prior NPP / Landscape approval stamp.

Final Status

Task End Date Reviewer's Name Type of Review Description
03/12/2010 GERARDO BONILLA OUT TO CUSTOMER Completed
03/12/2010 SUE REEVES REJECT SHELF Completed