Permit Number: T09BU01716
Parcel: 105102530

Address:
4280 N 1ST AV

Review Status: Completed

Review Details: GRADING

Permit Number - T09BU01716
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/30/2009 BIANCA RAMIREZ ENGINEERING REVIEW Denied DATE: November 30, 2009
SUBJECT: Grading
TO: Peter Salonga
LOCATION: 4280 N 1st Ave, T13S, R14E, Section 19, Ward 3
REVIEWERS: Bianca Ramirez, CFM
ACTIVITY: T09BU01716 (First Review)


RESUBMITTAL REQUIRED: Grading Plan, Drainage Statement and Geotechnical Report.

SUMMARY: Engineering Division of Development Services Department is unable to complete review of the proposed grading plan for the above referenced property. Engineering Division is requesting that copy of approved tentative plat and/or development plan be submitted prior to any further review. Please submit requested supplementary documentation accordingly and resubmit for full review.


If you have any questions, please contact me at bianca.ramirez@tucsonaz.gov or 520-837-4928.

Bianca Ramirez, CFM
Engineering Associate
12/04/2009 MICHAEL ST. PAUL ZONING REVIEW Denied December 4, 2009

Development Services Department
Zoning Review Section

Michael St.Paul
Planning Technician

T09BU01716 (Grading Plans for S05-207 Rillito Crossing Market Place)

Address: 4250 N 1st Ave


Comments:

1. The grading plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. It appears that the grading plan is in compliance with the approved development plan (Patricia Gehlen, September 22, 2009). Please submit one copy of the approved and stamped Development Plan, Landscape, and NPPO plans with the next grading plan submittal.

3. Provide a copy of an approved lot line reconfiguration using the lot split process.

4. Zoning will re-review the grading plan on the next submittal to ensure compliance with the approved development plan. Additional comments may be forthcoming.
12/07/2009 ANDREW CONNOR NPPO REVIEW Approv-Cond Ensure that all Engineering comments and concerns are addressed prior NPP / Landscape approval stamp.

Final Status

Task End Date Reviewer's Name Type of Review Description
12/11/2009 GERARDO BONILLA OUT TO CUSTOMER Completed
12/11/2009 SUE REEVES REJECT SHELF Completed