Permit Review Detail
Review Status: Completed
Review Details: GRADING
Permit Number - T09BU01687
Review Name: GRADING
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/19/2009 | ANDREW CONNOR | NPPO | REVIEW | Denied | 1. The site plan and landscape plan must show identical site layout to avoid conflict between the two plans. Ensure that all changes to the site plan are reflected on the landscape & grading plan. 2. After review of the grading, reference site plans and consulting with staff the loading zone indicated on the documents does not meet the minimum requirements of 12'x 35'. Revised site and landscape plans may be necessary contact Zoning reviewer for more information. 3. The grading application will be reviewed for compliance when the approved documents are included in the submittal. |
| 12/07/2009 | DAVID RIVERA | ZONING | REVIEW | Approved | |
| 12/07/2009 | PAUL MACHADO | ENGINEERING | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/07/2009 | BETH GRANT | OUT TO CUSTOMER | Completed |