Permit Number: T09BU01617
Parcel: 117200270

Address:
260 S CHURCH AV

Review Status: Completed

Review Details: TANKS

Permit Number - T09BU01617
Review Name: TANKS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/29/2009 STEVE SHIELDS ZONING REVIEW Passed
10/30/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved Provide a one line diagram showing service ground system. overcurrent protection on gen and chillers, overcurrent protection on chillers,and wiring methods to chillers.

RTMajuta
10/30/09
11/03/2009 MARTIN BROWN FIRE REVIEW Approved