Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T09BU01504
Parcel: 135074390

Review Status: Completed

Review Details: TANKS

Permit Number - T09BU01504
Review Name: TANKS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/22/2009 DAVE MANN FIRE REVIEW Denied FIre Comments

The distance to the emergency shut off is shown on the electrical plans as greater than 100 feet to the farthest dispenser. It is not shown at all in the tank submittal even though there are symbols for it. See IFC 2203.

Some sheets say there is secondary vapor recovery and some sheets have had it removed. Please clarify.
10/23/2009 TERRY STEVENS ZONING REVIEW Denied 10/23/2009

Development Services Department
Zoning Review Section

Terry Stevens
Lead Planner

Comments:

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. Zoning could not verify that the building plan was in compliance with the approved development plan. Please submit two copies of the approved and stamped development, landscape, and NPPO plans with the next building plan submittal.

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved site/development plan. Additional comments may be forthcoming.
10/27/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project T09BU01504, 1250 S Pantano Rd

Electrical plans denied, state and show compliance with NEC 2005 514.11 C. Where it will be and show distance on Electrical plans.

R T Majuta
Elect Pln Ck
PDSD City of Tucson
Ray.Majuta@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
11/06/2009 CPIERCE1 OUT TO CUSTOMER Completed