Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T09BU01488
Parcel: 13424436A

Address:
6301 E 22ND ST

Review Status: Completed

Review Details: GRADING

Permit Number - T09BU01488
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/05/2009 ANDREW CONNOR NPPO REVIEW Needs Review Ensure that all Engineering comments and concerns are addressed prior to NPP/Landscape approval stamp.
10/07/2009 JASON GREEN ENGINEERING REVIEW Denied DATE: October 7, 2009
SUBJECT: 6301 E 22nd Street- Engineering Review
TO: Robert Page
LOCATION: T14S R15E Sec18 Ward 4
REVIEWERS: Jason Green, CFM
ACTIVITY: T09CM02651 (Site Plan) and T09BU01488 (Grading Plan)

SUMMARY: Engineering Division of the Planning and Development Services Department has received and reviewed the proposed site plan (T09CM02651), grading plan (T09BU01488), and Storm Drainage Statement (Oracle Engineering Group, Inc., 01OCT09) for the above referenced property. Engineering Division does not recommend approval of the site plan or grading plan at this time. The following items need to be addressed:

STORM DRAINAGE STATEMENT COMMENTS:

1) Revise the Storm Drainage Statement (Statement) to label and detail all proposed drainage improvements. Specifically the proposed rock riprap pads adjacent to the depressed curb openings. In addition to the rock sizing and thickness provide filter fabric call out with specifications, the proposed slope, length and width dimensions of the pad, etc for construction purposes.

2) The property in located within a Shaded Zone X 100-year floodplain per the FIRM panel # 2253K, therefore is subject to the rules and regulations found in Chapter 26 of the Tucson Code. A Floodplain Use Permit will be required prior to grading plan approval and all notes and discussions must accurately reflect the flood zone determination. Elevation Certificates and inspections will be placed on the building permit applications for FFE requirements.

3) Revise or clarify the Statement with the Flood Hazard Notes on Sheet 0.1. Per Note #4, 5, and 6 the finished floor elevation of the proposed buildings must be elevated 1-foot above the calculated water surface elevation. Clarify in the Statement the WSEL and FFE requirements specifically addressing each elevation for both structures in order to complete the elevation certificate forms. Two elevation certificates (pre-slab inspection and final building inspection) are required for both buildings.

SITE PLAN COMMENTS:

4) DS Sec.2-02.2.1.A.8: Revise the site plan to show a minimum unobstructed radius of 5 feet at all PAAL intersections, unless the PAAL is designated as a fire lane or access for refuse collection then a minimum unobstructed radius of 18 feet is required per DS Sec.3-05.2.1.3.b. Specifically the PAAL intersection with the existing parking area associated with Pizza Hut.

5) DS Sec.2-02.2.1.A.11: Verify and label the 25-feet radii for both sides of the proposed driveway per City of Tucson Transportation Access Management Guidelines (TAMG), Section 5.5. Refer to DS Sec.3-01.3.2.C for street development standards. Standard driveway entrance design or reduced radii for curb returns will require prior written approval from TDOT Permits and Codes, contact Thad Harvison at 837-6592. Verify that the site plan sheets (Horizontal Control Sheet) and civil sheets match. Currently the Horizontal Control Sheet calls out a 15-foot radius for the west side of the proposed drive.

6) DS Sec.2-02.2.1.A.12: Revise the site plan to show the required 6-foot wide sidewalk with curbing along street frontages, Wilmot Road and 22nd Street. Per the adopted Mayor and Counsel policy all sidewalks along MS&R right-of-ways for arterial and collector streets require 6-foot wide sidewalks. Verify that the existing sidewalk meets the minimum requirements or provide an approved Development Standard Modification Request showing approval for the reduction in width.

7) DS Sec.2-02.2.1.A.12: Revise the site plan sheets and civil sheets to correctly label the required 5-foot pedestrian access adjacent to the PAAL and the north side of the proposed waiting/vending building. Per DS Sec.3-05.2.2.B.1 a pedestrian circulation must provide a clear 4-foot minimum width unless adjacent to a PAAL which would require a 5-foot width.

8) DS Sec.2-02.2.1.A.12: Revise the site plan to label all offsite handicap access ramps within the public right-of-way of both streets to be designed per the required Standard Detail for Public Improvement #207. Provide details and minimum slope requirements at all transitions from pedestrian circulation to vehicular circulation.

9) DS Sec.2-02.2.1.A.12: Refer to comments from Ron Brown, RA Structural Plans Examiner for all onsite handicap and ANSI Standard requirements that apply to this project.

10) DS Sec.2-02.2.1.A.15: Revise the Survey Note on Sheet 0.1 of the site plan. The Survey Note should state that the property is within a FEMA Shaded Zone X 100-year floodplain (not the 500-year as stated).

11) DS Sec.2-02.2.1.A.15: Revise the Flood Hazard Note # 3 on Sheet 0.1 of the site plan. The Note should state that the property is within a FEMA Shaded Zone X 100-year floodplain. Verification of FFE elevations must be provided within the revised Storm Drainage Statement.

12) DS Sec.2-02.2.1.A.16: Provide the Improvement Plan reference number for all existing drainage infrastructure adjacent to the site; i.e. catch basins, storm drains, grates, etc. All existing drainage improvements that are shown on the site plan must have the referenced improvement plan for site verification.

13) DS Sec.2-02.2.1.A.16: Revise Keynote #50 on Sheet 0.3 to correctly label the scupper height as 6-inches or 0.5 feet per the proposed Storm Drainage Statement.

14) DS Sec.2-02.2.1.A.20: Verify that all existing and proposed easements are drawn with recordation information, location, width, and purpose of on the site plan. Specifically the Permanent Service DR Easement per Book 9859, Page 1735 as shown on the subdivision plat map.

15) DS Sec.2-02.2.1.A.21: Provide dimensions from the street monument lines to the existing curb, sidewalk, driveways and utility lines for both Wilmot Road and 22nd Street.

16) DS Sec.2-02.2.1.A.32: Revise Keynote #33 on Sheet 0.3 to reference the correct detail for refuse construction. The Keynote should reference Detail 12 Sheet 0.5.

17) DS Sec.2-02.2.1.C: Revise the drainage arrows that are shown on the Landscape Plan to accurately show depressed curb locations and flow patterns to verify drainage into the proposed landscaping per the civil sheets.

18) Review and approval from TDOT Permits and Codes for all improvements within the public right-of-way will be required. A right-of-way use permit application will be required prior to construction. Refer to the following links for TDOT Forms and applications:

a) http://www.tucsonaz.gov/dsd/Forms_Fees___Maps/Applications/applications.html /

b) http://www.dot.ci.tucson.az.us/engineering/pia.php

c) Or contact Thad Harvison at 837-6592 for all additional questions regarding r-o-w.

19) Be advised that further comments may be forth coming on resubmittal of the site plan.

GRADING PLAN:

20) Provide a copy of the stamped approved site plan (T09CM02651). The grading plan can not be approved until verification that all details, locations, dimensions, and plan profiles match the approved site plan. Verify all information associated with the site plan is shown on the grading plan which will be used as the construction document.

21) Revise the civil sheet, keynote and Detail 4 to provide a specific construction detail for the proposed rock riprap pads at all depressed curb locations. In addition to the rock sizing and thickness provide filter fabric call out with specifications, the proposed slope, length and width dimensions of the pad, etc for construction purposes.

22) Provide additional spot elevation at the exit to the Car Wash Tunnel to verify that the majority of storm water runoff drains into the proposed depressed curb and landscape area and not through the PAAL.

23) Provide clarification for the two grates proposed at the Car Wash Tunnel's entrance and exit, verify they are connected to the mud/grease interceptor. Provide call out for pipe size, type and slope along with the required clean outs at junctions or angles greater than 10 degrees.

24) Provide the Improvement Plan reference number for all existing drainage infrastructure adjacent to the site; catch basins, storm drains, grates, etc. All existing drainage improvements that are shown on the grading plan must have the referenced improvement plan for site verification.

25) Revise Keynote #33 on Sheet G-1 to reference the correct detail for refuse construction. The Keynote should reference Detail 12 Sheet 0.5.

26) Provide the following note on the grading plan to read; "A floodplain use permit is required for all work proposed within the limits of the mapped FEMA Shaded Zone X 100-year floodplain as shown on the grading plan. Elevation Certificates will be required for all buildings to verify Finished Floor Elevations." Provide a Floodplain Use Permit application with the resubmittal of the grading plan for review and approval prior to grading plan approval.

27) Provide a General Note on Sheet G-1 to state; "All landscaping to be depressed minimum 6-inches for stormwater harvesting. Refer to the Water Harvesting Guidance Manual Ordinance # 10210 dated October 25 for further recommendations for stormwater harvesting."

28) Provide a General Note on Sheet G-1 to state; "Call for a Pre-construction meeting prior to start of earthwork. To schedule a DSD Pre-construction meeting, SWPPP inspection or general Engineering Inspections, call IVR (740-6970), or schedule with a Customer Service Representative at the Development Services Department, or contact DSD Engineering at 791-5550 extension 2101, or schedule inspections online at: http://www.ci.tucson.az.us/dsd/Online_Services/Online_Permits/online_permits.html

29) Please ensure that the grading plan is consistent with the site plan and Storm Drainage Report. Grading standards may be accessed at: http://www.ci.tucson.az.us/dsd/DevStandsTOC.pdf.

STORMWATER POLLUTION PREVENTION PLAN: A Storm Water Pollution Prevention Plan was not submitted for review.

30) Per the proposed civil sheets the site disturbance is greater than 1 acre therefore a Storm Water Pollution Prevention Plan (SWPPP) is required. The SWPPP must meet the minimum requirements of the AzPDES Construction General Permit (CGP).

31) Per City of Tucson Code Ordinance 10209, Chapter 26 Section 26-42.2: "For land disturbing activities that fall under the jurisdiction of this Article, a Stormwater Pollution Prevention Plan must be prepared and certified by an engineer, or a landscape architect and submitted along with the application for a grading permit to the City of Tucson Development Services Department." The SWPPP report and exhibits must be signed and sealed by the engineer of record or by a Registered Landscape Architect.

GENERAL COMMENTS:

Please provide a revised Storm Drainage Statement, site plan, grading plan, Floodplain User Permit application, and SWPPP that addresses the comments provided above. Include a comprehensive response letter addressing in detail responses to all of the above comments. Enclose "redlines" with the resubmittal package.

Further comments may be generated upon resubmittal of the site plan and grading plan review.

For questions, or to schedule an appointment, I can be reached at 837-4929.



Jason Green, CFM
Senior Engineer Associate
Engineering Division
COT Development Services
10/13/2009 TERRY STEVENS ZONING REVIEW Denied 10/15/2009

Development Services Department
Zoning Review Section

Terry Stevens
Lead Planner

Comments:

1. The grading plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. Zoning could not verify that the grading plan was in compliance with the approved site plan. Please submit two copies of the approved and stamped site, landscape, and NPPO plans with the next grading plan submittal.

3. Zoning will re-review the grading plan on the next submittal to insure compliance with the approved and stamped site plan. Additional comments may be forthcoming.

Final Status

Task End Date Reviewer's Name Type of Review Description
11/04/2009 CPIERCE1 OUT TO CUSTOMER Completed
11/04/2009 SUE REEVES REJECT SHELF Completed