Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T09BU01427
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/10/2009 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET S2.1; STRUCTURAL CALCULATIONS (PAGE 32): BEAM 47 IN THE STRUCTURAL CALCULATIONS IS LISTED AS A W21X44, WHILE ON THE PLAN IS A W18X35. CLARIFY. 2. SHEET S2.1; STRUCTURAL CALCULATIONS (PAGE 33): BEAM 73 IN THE STRUCTURAL CALCULATIONS IS LISTED AS A W21X44, WHILE ON THE PLAN IS A W18X40. CLARIFY. 3. SHEET S2.1: THERE ARE SEVERAL BEAMS IN THE LAB AREA THAT HAVE LARGER SIZES INDICATED THAN LISTED IN THE STRUCTURAL CALCULATIONS (FOR EXAMPLE, 56, 66, 80). PLEASE REVIEW THIS AREA AND PROVIDE REVISED CALCULATIONS AS REQUIRED. 4. SHEET S2.3; STRUCTURAL CALCULATIONS (PAGE 23): BEAM 15 IN THE STRUCTURAL CALCULATIONS IS LISTED AS A W21X44, WHILE ON THE PLAN IS A W18X35. CLARIFY. 5. SHEET S2.3; STRUCTURAL CALCULATIONS (PAGE 24): BEAM 55 IN THE STRUCTURAL CALCULATIONS IS LISTED AS A W21X48, WHILE ON THE PLAN IS A W18X35. CLARIFY. 6. SHEET S2.3; STRUCTURAL CALCULATIONS (PAGE 25): BEAM 87 IN THE STRUCTURAL CALCULATIONS IS LISTED AS A W21X50, WHILE ON THE PLAN IS A W21X44. CLARIFY. 7. SHEET S2.4 (PENTHOUSE ROOF); STRUCTURAL CALCULATIONS (PAGE 21): BEAM 10 IN THE STRUCTURAL CALCULATIONS IS LISTED AS A W16X26, WHILE ON PLAN IS A HSS10X6X1/4. CLARIFY. 8. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/13/2010 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |
| 01/13/2010 | SUE REEVES | REJECT SHELF | Completed |