Permit Number: T09BU01427
Parcel: 10706027E

Review Status: Completed

Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG

Permit Number - T09BU01427
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/25/2009 RONALD BROWN ADA REVIEW Passed No accessibility requirements for foundation work only
09/28/2009 DAVE MANN FIRE REVIEW Approved
09/28/2009 JASON GREEN ENGINEERING REVIEW Approved
09/29/2009 STEVE SHIELDS ZONING REVIEW Approved
10/14/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET S1.0 (CONCRETE NOTE 1); STRUCTURAL CALCULATIONS (PAGE 93): THE CALCULATION INDICATES THE CONCRETE DESIGN STRENGTH OF 3 KSI, WHILE THE NOTE ON SHEET S1.0 INDICATES THE FOUNDATION DESIGN STRENGTH OF 2500 PSI. CLARIFY.
2. SHEET S2.0; STRUCTURAL CALCULATIONS PAGE 91: THE COLUMN FOOTING AT 98-AA IS LISTED AS 7'-0"X7'-0"X1'-6" IN THE CALCULATIONS, BUT IS CALLED OUT AS F8 (6'-0"X6'-0"X1'-6") ON S2.0. VERIFY.
3. SHEET S2.0; STRUCTURAL CALCULATIONS PAGE 92: THE COLUMN FOOTING AT L-6 IS LISTED AS 9'-0"X9'-0"X2'-0" IN THE CALCULATIONS, BUT IS CALLED OUT AS F9 (7'-0"X7'-0"X1'-6") ON S2.0. VERIFY.
4. SHEET S2.0; STRUCTURAL CALCULATIONS PAGE 92: THE COLUMN FOOTING AT H-4 IS LISTED AS 9'-0"X9'-0"X2'-0" IN THE CALCULATIONS, BUT IS CALLED OUT AS F10 (8'-0"X8'-0"X1'-6) ON S2.0. VERIFY.
5. SHEET S2.0: DID NOT FIND STRUCTURAL CALCULATIONS FOR THE COLUMNS OR FOOTINGS ON GRID 8.1 (3 THUS). CLARIFY.
6. GENERAL: PLEASE PROVIDE A REFERENCE PAGE IN THE STRUCTURAL CALCULATIONS FOR THE CONTINUOUS FOOTING DESIGNS BEGINNING ON PAGE 93. THE LAYOUT ON PAGE 90 IS UNREADABLE.
7. GENERAL: THE COLUMN AND COLUMN FOOTING DESIGNS CAN TYPICALLY BE REVIEWED EASILY WHERE THE COLUMN/FOOTING FALLS DIRECTLY ON GRID LINES. COLUMNS AND FOOTINGS THAT ARE IDENTIFIED DIMENSIONALLY (COLUMN LINE 668.22 FT-24.08 FT) ARE DIFFICULT TO REVIEW. PLEASE CLARIFY.
8. GENERAL: PLEASE REVIEW THE COLUMNS AND COLUMN FOOTINGS, AND COORDINATE THE STRUCTURAL CALCULATION DESIGNS WITH THE DRAWINGS/SCHEDULES.
9. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.