Permit Number: T09BU01412
Parcel: 13711429H

Review Status: Completed

Review Details: TANKS

Permit Number - T09BU01412
Review Name: TANKS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/06/2009 MARTIN BROWN FIRE REVIEW Approved
10/14/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project: 1715 W Irvington Rd
T09BU01412
New Underground Fuel Tanks

The Electrical Plans have been denied for the following:
1. The Electrical sheets are required to be sealed by an engineer.
2. Provide the plans for the main project which show how these tanks are fed.

Ray T Majuta
Elect PLan Ck
PDSD City of Tucson
10/14/09
Ray.Majuta@tucsonaz.gov
10/15/2009 STEVE SHIELDS ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
10/26/2009 CINDY AGUILAR OUT TO CUSTOMER Completed
10/26/2009 SUE REEVES REJECT SHELF Completed