Permit Number: T09BU01232
Parcel: 105101270

Address:
450 E WETMORE RD

Review Status: Completed

Review Details: GRADING

Permit Number - T09BU01232
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/03/2009 ANDREW CONNOR NPPO REVIEW Passed
09/18/2009 RONALD BROWN ZONING HC REVIEW Denied Some confusion here. Sheet A1.1 shows new basket ball court and civil sheet 2 of 2 shows all parking. Please redesign and make corrections as to which direction to go.
09/18/2009 LOREN MAKUS ENGINEERING REVIEW Denied September 18, 2009
T09BU01232
Amphi Land Lab Drainage
Grading permit review

The permit cannot be approved as submitted. Revise the plans and report to address the following comments.

1. In the drainage report, discuss any off site drainage that affects the parcel. Clearly describe the amount of water held by the proposed walls and demonstrate that it will be adequately managed.
2. Clearly indicate the scope and nature of work. On all plans sheets indicate what is existing and what is proposed. Ensure that the plans are consistent in depiction of pavement marking and striping. For example the site sheets show basketball striping and a ramp where the grading sheets show parking spaces.
3. Show how the drainage from all areas of the site and any offsite flows will be managed on the site.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/01/2009 CPIERCE1 OUT TO CUSTOMER Completed
10/01/2009 SUE REEVES REJECT SHELF Completed