Review Details: GRADING

Permit Number - T09BU01039
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/24/2009 MICHAEL ST. PAUL ZONING REVIEW Denied July 24, 2009

Development Services Department
Zoning Review Section

Michael St.Paul
Planning Technician

T09BU01039 Grading Plans for T08CM03344


Comments:

1. The grading plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. The grading plan appears to be in compliance with the approved site plan. Please provide one copy of the stamped approved site plan with your next submittal.

3. Zoning will re-review the grading plan on the next submittal to ensure compliance with the approved site plan. Additional comments may be forthcoming.
08/05/2009 ANDREW CONNOR NPPO REVIEW Denied Ensure that all Engineering comments and concerns are addressed prior to NPP/Landscape approval.

Include a copy of the approved landscape plan.
08/12/2009 LOREN MAKUS ENGINEERING REVIEW Approved To: Design-Construction-Consultants DATE: July 22, 2009
2828 N. Country Club Rd., Ste. 100
Tucson, Arizona 85716
SUBJECT: Lucky Wishbone, 4701 E. Broadway Blvd.
Grading Plan T09BU01039 (First Review)
T14S, R14E, Section 11

RESUBMITTAL REQUIRED: Grading Plan and Drainage Report.

The Grading Plan (GP) and Drainage Report (DR) Plan cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Grading Plan:
1. Please include a response letter to the comments along with the corrected copies of the GP.
2. Remove the "Preliminary Review" stamp across the engineers seal.
3. Complete Grading plan number (T09BU01039).
4. All SVT's shall be shown on the grading plan (future and existing). This includes the future face of curb. See redlines.
5. Provide pedestrian access to the refuse enclosure from the proposed building.
6. Show a distance between the landscape area at the NE corner of the new building and the center of the concrete flow gutter.
7. Call out the grade breaks at both entrances.
8. Provide additional elevations and/or drainage arrows with the percent slopes for the north parcel.
9. Call out the surface material adjacent to the 12'x35' loading zone.
10. Add the book and page for the basis of elevation.
11. Provide depressed curbs at the landscape water harvesting areas in order to receive stormwater (typ).
12. Show typical cross section of P.A.A.L. with transverse and longitudinal slopes.
13. A permit or a private improvement agreement might be necessary for any work performed within the Right-of-way. Contact Permits and Codes at (520) 791-5100 for permit information.
14. Cut or fill slopes require a 2' minimum setback from property line.

Drainage report:
1. The DR has been conditionally accepted with one remaining comment.
2. Replace the COT Activity #D08-XXXX on the cover sheet of the DR with the grading plan number (T09BU01039) and the site plan number (T08CM03344)

If you have any questions, I can be reached at 837-4932 or Paul.Machado@tucsonaz.gov
Paul P. Machado
Senior Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 837-4932 office
(520) 879-8010 fax
C:/4701 E. Broadway Blvd Grad
08/12/2009 LOREN MAKUS ENGINEERING REVIEW Approved A revised plan meeting the requirements for approval was brought in and reviewed.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/12/2009 CINDY AGUILAR OUT TO CUSTOMER Completed
08/12/2009 SUE REEVES REJECT SHELF Completed