Permit Review Detail
Review Status: Completed
Review Details: POOL:COMM-MODEL
Permit Number - T09BU01027
Review Name: POOL:COMM-MODEL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/20/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 07/20/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 08/05/2009 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Project: 801 W Miracle Mile T09BU01027 New Pool The Electrical Plans for the pool have been denied for the following: 1. Provide the location and name of the Panel the electrical circuits for equipment will be connected to. 2. List the circuits the equipment will be assigned to, conductor sizes, conduit sizes and loads. 3. General note # 9 indicates a 400 watt light, where will it be installed ? Provide a cut sheet of this fixture. 4. Show GFCI protection for any light in the pool.(2005 NEC 680-23. 5. Provide a note on plan to indicate Grounding for pool to comply with 2005 NEC 680-26. 6. Provide note on plan installation to comply with 2005 NEC 680--Pools. Ray T Majuta Electrical Plan Check PSDS City of Tucson 8/6/09 Ray.Majuta@tucsonaz.gov |
| 08/10/2009 | DAVID RIVERA | ZONING | REVIEW | Denied | DSD TRANSMITTAL FROM: David Rivera Principal Planner PROJECT: T09BU01027 801 W Miracle Mile Road Ghost Ranch Site- Proposed New Pool TRANSMITTAL DATE: August 10, 2009 COMMENTS: Please resubmit revised drawings along with redlines and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed. 1. Zoning has reviewed the proposed pool plans but cannot approve them until a copy of the approved and stamped site plan is included with the pool application and drawing package. There are several items remaining on the site plan that have to be revised and therefore the plan accompanying the pool application is not current. 2. Zoning will re-review the pool permit again to ensure compliance with the approved and stamped site plan. Zoning is also willing to review and approve the pool permit and plans over the counter with an appointment when approved and stamped site plan is included. If you have any questions about this transmittal, please call David Rivera, (520) 791-5608. C:\planning\cdrc\DSD\T09BU01027.doc RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Provide a copy of the approved and stamped site plan with the pool plan package. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/02/2009 | CPIERCE1 | OUT TO CUSTOMER | Completed |
| 09/02/2009 | CPIERCE1 | REJECT SHELF | Completed |