Permit Review Detail
Review Status: Completed
Review Details: TENTS
Permit Number - T09BU00947
Review Name: TENTS
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/29/2009 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | Project: T09BU00947 3800 W Starr Pass Tent--Temp. The Electrical Plans have been denied for the following; 1. How will the transition in wiring method be made from the 400A disconnect to the four 25 ton units. 2. Same for the 200A disconnect to the 2 25 ton units. 3. Total load calculations show only 5 ac units. 4. Show wiring methods to individual units from disconnects. Ray T Majuta DSD City of Tucson Elect Plan Ck 6/29/09 520/837/4988 |
| 06/30/2009 | DAVE MANN | FIRE | REVIEW | Approved |