Review Details: RESUBMITTAL - GRADING ALL
Permit Number - T09BU00917
Review Name: RESUBMITTAL - GRADING ALL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/11/2009 | DAVID RIVERA | ZONING | REVIEW | Denied | DSD TRANSMITTAL FROM: David Rivera Principal Planner PROJECT: T09BU00917 - Revision 1 801 W Miracle Mile Ghost Ranch Lodge Multi-Family Dwelling Use Grading Plan TRANSMITTAL DATE: December 11, 2009 Zoning cannot approve the grading plan until the site plan has been approved. |
| 12/16/2009 | LOREN MAKUS | ENGINEERING | REVIEW | Denied | December 17, 2009 T09CM01333 and T09BU00917 Site and Grading Revision 1. Update the details in the revised grading and drainage plan to reflect the acquisition of Glaris Avenue. 2. Clearly show how water will be directed to the landscape areas for water harvesting. Provide curb openings to allow runoff to enter the landscape areas. 3. Show how the landscape areas will be depressed to maximize water harvesting. 4. The new concrete swale along the former Glaris Avenue alignment doesn't allow for water harvesting or landscaping in this area. Provide analysis to show that the concrete swale is necessary or replace with another surface treatment that provides for landscaping and water harvesting. |
| 12/21/2009 | ANDREW CONNOR | NPPO | REVIEW | Approv-Cond | Ensure that all Engineering comments and concerns are addressed prior NPP / Landscape approval stamp. |