Permit Number: T09BU00917
Parcel: 10705126B

Review Status: Completed

Review Details: GRADING

Permit Number - T09BU00917
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/24/2009 DAVID RIVERA ZONING REVIEW Denied 06/24/2009

Development Services Department
Zoning Review Section

David Rivera
Principal Planner

Comments:

1. The grading plan has been reviewed by Zoning Review Section but cannot approve the plan at this time.

2. Zoning could not verify that the grading plan was in compliance with the DSD approved and stamped site plan. Please submit two copies of the DSD approved and stamped site plan, landscape, and NPPO plans with the next grading plan submittal.

3. Zoning will re-review the grading plan on the next submittal to ensure compliance with the DSD approved and stamped site plan and landscape/NPPO plans. Additional comments may be forthcoming.

Please ensure that the grading plan matches the DSD approved and stamped site plan.
07/06/2009 ANDREW CONNOR NPPO REVIEW Denied Submit a copy of the approved site plan and landscape plans for reference. The grading application will be reviewed for compliance when the approved documents are included in the submittal. Revise grading plan as necessary to comply with approved plans.
07/16/2009 LOREN MAKUS ENGINEERING REVIEW Denied July 22, 2009
T09BU00917
Grading Permit Review


1. Clearly indicate the areas that will be graded by providing grading limits on the plan view.
2. Provide dimensions on the plan view for all features including sidewalks, PAALs, driveways, and landscaping areas, for example. Even though the plans are drawn to scale, the plans must be fully dimensioned. Note that the sidewalks must be at least 6 feet wide in addition to the width of the curb where they abut parking spaces without wheel stops.
3. Revise the solid waste enclosure detail to meet the development standards. The side walls also must be protected by bollards and provide 10 feet clear.
4. The plan shows significant construction of private features, such as screen walls and PAALs within the right-of-way. Provide recordation and documentation of approval for this work.
5. The grading plan will not be approved until the site plan has been approved. Make sure that the site plan and grading plan are consistent.

Final Status

Task End Date Reviewer's Name Type of Review Description
09/02/2009 SUE REEVES OUT TO CUSTOMER Completed