Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T09BU00781
Parcel: 13316021B

Address:
6616 E GRANT RD

Review Status: Completed

Review Details: RESUBMITTAL - GRADING ALL

Permit Number - T09BU00781
Review Name: RESUBMITTAL - GRADING ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/13/2009 ANDREW CONNOR NPPO REVIEW Approv-Cond
08/14/2009 LOREN MAKUS ENGINEERING REVIEW Denied August 14, 2009
T09BU00781
Grading Plan Review
The grading plan cannot be approved as submitted. Please address the following comments.

1. Show the Sight Visibility Triangles for both sides of the exit driveway and for the driveway adjacent to this project. This is required to demonstrate that the features of this project don't adversely affect the adjacent driveway.
2. Show sufficient details and spot elevations to demonstrate that the water harvesting areas will function to collect water.
3. Provide a detail showing the relationship between the buildings on the adjacent site and the development on this site. Show location of any perimeter wall relative to the property lines and all vehicle use areas. Also show grades or provide contours on adjacent sites.
4. The grading plan cannot be approved until the site plan is approved. Update the grading plan to reflect any changes to the site plan.
08/27/2009 STEVE SHIELDS ZONING REVIEW Denied GRADING PLAN CANNOT BE APPROVED UNTIL THE SITE PLAN HAS BEEN APPROVED.