Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL NEW
Permit Number - T09BU00695
Review Name: COMMERCIAL NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/20/2009 | DAVE MANN | FIRE | REVIEW | Denied | Fire sprinklers required. No fire flow available in this area. Refer to 2006 IFC, appendix B,Section B104, B105. Please include the following fire sprinkler design criteria to the plans. 1. Flow data from tanks and pumps. 2. The standard to be used in development of sprinkler system. (NFPA 13, NFPA 13R, or NFPA 13D) 3. The hazard classification of the building, including any special hazards. 4. The density required of the water supply. |
| 08/21/2009 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 08/28/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 08/28/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 08/28/2009 | RSHERRY1 | WWM | REVIEW | Passed | No waste water fixtures. |
| 08/28/2009 | ROBERT SHERRY | WATER | REVIEW | Passed | |
| 09/15/2009 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Passed |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/18/2009 | THAUSER1 | OUT TO CUSTOMER | Completed |