Permit Review Detail
Review Status: Completed
Review Details: SITE
Permit Number - T09BU00695
Review Name: SITE
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/04/2009 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 08/10/2009 | PETER MCLAUGHLIN | LANDSCAPE | REVIEW | Approved | |
| 08/10/2009 | PETER MCLAUGHLIN | NPPO | REVIEW | Approved | |
| 08/19/2009 | SREEVES1 | ADA | REVIEW | Passed | |
| 08/20/2009 | DAVE MANN | FIRE | REVIEW | Denied | Fire sprinklers required. No fire flow available in this area. Refer to 2006 IFC, appendix B,Section B104, B105. Please include the following fire sprinkler design criteria to the plans. 1. Flow data from tanks and pumps. 2. The standard to be used in development of sprinkler system. (NFPA 13, NFPA 13R, or NFPA 13D) 3. The hazard classification of the building, including any special hazards. 4. The density required of the water supply. |
| 08/21/2009 | RONALD BROWN | ZONING HC SITE | REVIEW | Approved | |
| 08/28/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/18/2009 | THAUSER1 | OUT TO CUSTOMER | Completed |