Permit Number: T09BU00547
Parcel: 10306092G

Review Status: Completed

Review Details: GRADING

Permit Number - T09BU00547
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/03/2009 PAUL MACHADO ENGINEERING REVIEW Denied To: Brown and Caldwell DATE: June 4, 2009
110 S. Church Ave.
Tucson, Arizona 85701
SUBJECT: Roger Rd. WRF to Ina Rd WRF, 2560 W. Sweetwater Dr.
Grading Plan T09BU00547 (Second Review)
T13S, R13E, Section 20

RESUBMITTAL REQUIRED: Grading Plan.

The Grading Plan (GP) cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Grading Plan:
1. Please include a response letter to the comments along with the corrected copies of the GP.
2. The GP cannot be approved prior to the approval of the FUP.
3. A flood plain use permit is required for this project. Apply for the FUP with the re-submittal. Per previous comment.

SWPPP:
1. The SWPPP has been accepted by engineering.

If you have any questions, I can be reached at 837-4932 or Paul.Machado@tucsonaz.gov
Paul P. Machado
Senior Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 837-4932 office
(520) 879-8010 fax
C:/2560 W. Sweetwater Dr Grad & SWPPP 2.doc
06/05/2009 DROBEY1 ZONING REVIEW Needs Review
06/05/2009 DROBEY1 NPPO REVIEW Needs Review