Permit Number: T09BU00486
Parcel: 125130650

Address:
3148 E 2ND ST

Review Status: Completed

Review Details: GRADING

Permit Number - T09BU00486
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/13/2009 TERRY STEVENS ZONING REVIEW Denied Grading notes for permits plus.
With SITE PLAN

04/13/2009

Development Services Department
Zoning Review Section

Terry Stevens
Lead Planner

Comments:

1. The grading plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. Zoning could not verify that the grading plan was in compliance with the approved site plan. Please submit two copies of the approved and stamped site, landscape, and NPPO plans with the next grading plan submittal.

3. Zoning will re-review the grading plan on the next submittal to insure compliance with the approved and stamped site plan. Additional comments may be forthcoming.
04/17/2009 BIANCA RAMIREZ ENGINEERING REVIEW Denied DATE: April 17, 2009
SUBJECT: Grading
TO: Wally Gasser
LOCATION: 3148 E 2nd Street, T14S, R14E, Section 9, Ward 6
REVIEWERS: Bianca Ramirez, CFM
ACTIVITY: T09BU00486 (Second Review)


RESUBMITTAL REQUIRED: Grading Plan

SUMMARY: Engineering Division of Development Services Department has received and reviewed the proposed grading plan for the above referenced property. Engineering Division does not recommend approval of the grading plan at this time. Please address the following review comments prior to the next submittal.

Please include a response letter to the comments along with the corrected copies of the Grading Plan.

Grading Plan:

1. Complied
2. Complied
3. Verify accuracy of legal disruption. Acknowledge lot combo in progress.
4. Verify that all text is a minimum of 12 point font throughout plan set. Specifically the text within location map on sheet C-1.
5. Clearly indicate Cut and Fill quantities in cubic yards Separate out and include total.
6. Complied
7. A permit or a private improvement agreement will be necessary for any work performed within the Right-of-way. Contact Permits and Codes at (520) 791-5100 for permit information.
8. Complied
9. Complied
10. Noted
11. Complied
12. Please label lot dimensions and bearings per D.S. 2-02.2.1.5. Current dimensions of lot do not match the parcel outline being shown in MapGuide. Or provide documentation for lot combo. Acknowledge lot combo in progress
13. Complied
14. Label existing and future sight visibility triangles per D.S. 2-02.2.1.10. Provide proof from the transportation department that there is on street parking. An email to Bianca Ramirez @ bianca.ramirez@tucsonaz.gov will suffice. Verify that all SVT's are dimensioned correctly.
15. Complied
16. Noted
17. Complied
18. Complied
19. Complied
20. DS Sec. 2-05.2.4.H.2: Provide the right-of-way (ROW) recordation information for Anderson Blvd and 2nd Street. Response letter includes book and page. Please provide on plan set.
21. Verify that all easement of record are graphically shown on the plan together with recording docket and page per D.S. 2-02.2.1.20.
22. Complied
23. Complied
24. Complied
25. See Zoning comments.
26. See refuse contained detail previously enclosed and ensure that all components are called out within detail in accordance with the detail. Concrete approach slab.
27. A permit or a private improvement agreement will be necessary for any work performed within the Right-of-way. Contact Permits and Codes at (520) 791-5100 for permit information.
28. Complied
29. Additional comments may be forthcoming.

If you have any questions, I can be reached at 837-4928 or Bianca.Ramirez@tucsonaz.gov

Bianca C. Ramirez
Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 837-4928
04/20/2009 CAGUILA1 NPPO REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
04/20/2009 CINDY AGUILAR OUT TO CUSTOMER Completed