09/14/2009 JASON GREEN ENGINEERING REVIEW Approv-Cond DATE: September 14, 2009
SUBJECT: America's Best Self Storage Grading Plan- 4th Engineering Review
TO: Scott Strum
LOCATION: T15S R15E Sec21, Ward 4
REVIEWERS: Jason Green, CFM
ACTIVITY: T09BU00442 (Grading Plan)

SUMMARY: Engineering Division of Development Services Department has received and reviewed the revised grading plan (T09BU00442), Drainage Report (Patterson Hydrology Drainage Engineering, Inc., 01AUG08, revised 31JUL08) and Stormwater Pollution Prevention Plan (Patterson Hydrology Drainage Engineering, Inc., 10JUL09) for the above referenced property. Engineering Division recommends conditional approval of the grading plan application at this time. The following items need to be addressed prior to stamp grading plan approval:

GRADING PLAN COMMENTS:

1) Restated: Provide a copy of the last stamped approved Development Plan (D08-0021). The grading plan can not be stamp approved until verification that all details, locations, dimensions, and plan profiles match the approved Development Plan.

2) Complied.

3) Complied.

4) Complied.

5) Complied.

6) Complied.

7) Complied.

8) Acknowledged.

9) Complied.

10) Acknowledged.

11) Acknowledged.


STORMWATER POLLUTION PREVENTION PLAN: The proposed SWPPP meets the minimum requirements of the AzPDES Construction General Permit (CGP). However the SWPPP and Exhibits can not be stamped approved until approval of the grading plan. Provide both copies with resubmittal for stamp approval:

12) Complied.

13) Complied.

14) Complied.

15) Complied.

16) Complied.

17) Complied.

18) Complied.

19) Complied.

20) Complied.

GENERAL COMMENTS:

Provide the last approved Development Plan, 2 sets of the grading plan, and 3 SWPPP reports for stamp approval.

For questions I can be reached at 837-4929.

Jason Green, CFM
Senior Engineer Associate
Engineering Division
COT Development Services