Permit Number: T09BU00315
Parcel: 131100330

Address:
5502 E 22ND ST

Review Status: Completed

Review Details: TANKS

Permit Number - T09BU00315
Review Name: TANKS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/23/2009 MICHAEL ST. PAUL ZONING REVIEW Approved
03/23/2009 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved 1) PLEASE SHOW ON SITE PLAN LOCATION, ROUTING, CONDUIT SIZE AND CONDUCTOR SIZES FOR TANK AND EMERGENCY SHUT-OFF.
2) PLEASE SHOW PANEL SCHEDULE AND INDICATE IF NEW CIRCUIT OR IF USING AN EXISTING.
3) IF EXISTING CIRCUIT THEN SHOW ALL LOADS ON CIRCUIT.
4) STRUCTURAL CALCULATIONS REQUIRED FOR TALL TANK AND FOOTINGS. STRUCTURAL REVIEW WILL BE REQUIRED.
5) PLEASE ENLARGE PLANS FOR BETTER LEGIBILITY.
03/25/2009 MARTIN BROWN FIRE REVIEW Approved
03/26/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. PROVIDE LATERAL AND VERTICAL ANALYSIS TO DETERMINE REQUIRED FOUNDATION SIZE AND CONNECTION OF TANK TO FOUNDATION. PROVIDE DRAWINGS. CALCULATIONS AND DRAWINGS TO BE STAMPED AND SIGNED BY A LICENSED ENGINEER.