Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T08PL01682
Parcel: 10612031C

Address:
3426 N ROMERO RD

Review Status: Completed

Review Details: PLUMBING

Permit Number - T08PL01682
Review Name: PLUMBING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/19/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Reduced pressure backflow prevention assemblies, not double check valve assemblies are required at the water meter for multi-metered properties. Reference: COT Ordinance 9976, http://www.tucsonaz.gov/water/docs/backflow-ord.pdf
2. Provide calculations to show that the water distribution system can provide a minimum of 20 PSI to each mobile home service connection at the maximum operating conditions. Reference: Section E16, Appendix E, UPC 2006.
3. Show that the maximum flow velocity in the piping will not exceed 8 feet per second at the maximum operating conditions. Reference: Section E17, Appendix E, UPC 2006 and Section 210.1, IAPMO Installation Standard 8-2003, UPC 2006.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/22/2009 SUE REEVES OUT TO CUSTOMER Completed
01/22/2009 SUE REEVES REJECT SHELF Completed