Permit Review Detail
Review Status: Completed
Review Details: PLUMBING
Permit Number - T08PL01682
Review Name: PLUMBING
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/19/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Reduced pressure backflow prevention assemblies, not double check valve assemblies are required at the water meter for multi-metered properties. Reference: COT Ordinance 9976, http://www.tucsonaz.gov/water/docs/backflow-ord.pdf 2. Provide calculations to show that the water distribution system can provide a minimum of 20 PSI to each mobile home service connection at the maximum operating conditions. Reference: Section E16, Appendix E, UPC 2006. 3. Show that the maximum flow velocity in the piping will not exceed 8 feet per second at the maximum operating conditions. Reference: Section E17, Appendix E, UPC 2006 and Section 210.1, IAPMO Installation Standard 8-2003, UPC 2006. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/22/2009 | SUE REEVES | OUT TO CUSTOMER | Completed |
| 01/22/2009 | SUE REEVES | REJECT SHELF | Completed |