Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T08PL01106
Parcel: 117101280

Address:
283 N STONE AV

Review Status: Completed

Review Details: PLUMBING

Permit Number - T08PL01106
Review Name: PLUMBING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/23/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Reduced pressure backflow prevention assemblies are required at the water meter for multi-use commercial buildings. A Watts model 007 is not approved for this use. Reference: COT Ordinance 9976, http://www.tucsonaz.gov/water/docs/backflow-ord.pdf