Permit Number: T08PL00073
Parcel: 14118530A

Review Status: Completed

Review Details: PLUMBING

Permit Number - T08PL00073
Review Name: PLUMBING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/14/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide drawings for the private sewer collection system that have been approved by the Pima County Department of Environmental Quality.
2. The rim elevation of the next upstream sanitary manhole (2965.80) is higher than the first floor elevation (2960.00). Provide a backwater valve per Section 710.1, UPC 2006, as amended by the City of Tucson.