Permit Review Detail
Review Status: Completed
Review Details: PLUMBING
Permit Number - T08PL00073
Review Name: PLUMBING
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/14/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide drawings for the private sewer collection system that have been approved by the Pima County Department of Environmental Quality. 2. The rim elevation of the next upstream sanitary manhole (2965.80) is higher than the first floor elevation (2960.00). Provide a backwater valve per Section 710.1, UPC 2006, as amended by the City of Tucson. |
| 03/14/2008 | CPIERCE1 | WWM | REVIEW | Needs Review |