Plan Number: T08PI00022
Parcel: Unknown

Address:
3301 S 6TH AV

Review Status: Completed

Review Details: PIA RESUBMITTAL

Plan Number - T08PI00022
Review Name: PIA RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/05/2009 Blanca Espino DOT ENGINEERING REVIEW Approved PIA Plan
1. Please include a detail letter of explanation with the next submittal indicating where and how revisions were made. Single word responses are unacceptable. Include plans/redlines from previous plan submittal.

2. Sheet 2, Indicate the Book and Page numbers for the ROW dedication. See redlines.

3. Sheet 2, Construction Note # 6 proposes a Concrete Valley Gutter (CVG). Indicate the Beginning & Ending CVG, include Stationing, Offset & Elevation. Draw the CVG to its exact boundaries on the plan view. See redlines.

4. You can email me a PDF drawing once you have addressed the above comments so that I can approve the plan and give you the "Ok" for the mylar submittal ONLY IF THE OTHER TDOT SECTIONS APPROVE THE PLAN AS WELL.
01/09/2009 SMONTIE1 UTILITY CLEARANCES COT STREETS DIVISION Completed Please submit utility clearance letters.
01/09/2009 SMONTIE1 UTILITY CLEARANCES COT WATER NEW DEVELOPMENT Completed Please submit utility clearance letters.
01/09/2009 SMONTIE1 UTILITY CLEARANCES PC WASTEWATER MGMT Completed Please submit utility clearance letters.
01/09/2009 SMONTIE1 UTILITY CLEARANCES QUEST COMMUNICATION Completed Please submit utility clearance letters.
01/09/2009 SMONTIE1 UTILITY CLEARANCES TUCSON ELECTRIC POWER CO Completed Please submit utility clearance letters.
01/09/2009 SMONTIE1 UTILITY CLEARANCES COX COMMUNICATION Completed Please submit utility clearance letters.
01/09/2009 SMONTIE1 UTILITY CLEARANCES SOUTHWEST GAS CORP Completed Please submit utility clearance letters.
01/12/2009 GARY WITTWER DOT LANDSCAPE REVIEW Approved This is approved, but the notes are weak. You have put it all on the contractor to figure out.
01/13/2009 JOSE ORTIZ DOT TRAFFIC REVIEW Approved
01/20/2009 LANCE PETERSON DOT STREET MAINTENANCE REVIEW Approved
01/23/2009 TAMI HAUSER PIA COORDINATOR CUSTOMER CALLED; PLANS @ AMBASSADOR Completed
01/23/2009 TAMI HAUSER PIA COORDINATOR OUT TO CUSTOMER Completed
12/24/2008 SMONTIE1 UTILITY CLEARANCES EL PASO NATURAL GAS Passed Please submit utility clearance letters.
12/24/2008 SMONTIE1 UTILITY CLEARANCES KINDER MORGAN ENERGY Passed Please submit utility clearance letters.