Plan Number: T08PI00019
Parcel: Unknown

Review Status: Completed

Review Details: PIA SUBMITTAL

Plan Number - T08PI00019
Review Name: PIA SUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/14/2008 SMONTIE1 UTILITY CLEARANCES COT STREETS DIVISION Denied Please submit utility clearance letters.
05/14/2008 SMONTIE1 UTILITY CLEARANCES COT WATER NEW DEVELOPMENT Denied Please submit utility clearance letters.
05/14/2008 SMONTIE1 UTILITY CLEARANCES PC WASTEWATER MGMT Denied Please submit utility clearance letters.
05/14/2008 SMONTIE1 UTILITY CLEARANCES QUEST COMMUNICATION Denied Please submit utility clearance letters.
05/14/2008 SMONTIE1 UTILITY CLEARANCES TUCSON ELECTRIC POWER CO Denied Please submit utility clearance letters.
05/14/2008 SMONTIE1 UTILITY CLEARANCES COX COMMUNICATION Denied Please submit utility clearance letters.
05/14/2008 SMONTIE1 UTILITY CLEARANCES SOUTHWEST GAS CORP Denied Please submit utility clearance letters.
05/14/2008 SMONTIE1 UTILITY CLEARANCES EL PASO NATURAL GAS Denied Please submit utility clearance letters.
05/14/2008 SMONTIE1 UTILITY CLEARANCES KINDER MORGAN ENERGY Denied Please submit utility clearance letters.
05/21/2008 GARY WITTWER DOT LANDSCAPE REVIEW Approv-Cond Please address the Native Plant Preservation Ordinance. It would appear that no native plants will be impacted by the PIA work. Please confirm and address appropriately. Exception letter if no impacts.
05/22/2008 RICHARD LEIGH DOT ENGINEERING REVIEW Denied May 22, 2008

SUBJECT: Simpson St., Granada Av., and Cushing St. Improvements, PIA T08PI0019

PROJECT REVIEWER: Richard Leigh, DOT, Permits and Codes Section

RESUBMITTAL REQUIRED: Permits and Codes Section has reviewed the PIA Plan and does not recommend approval of the PIA Plan at this time. The following comments need to be addressed in the next submittal.

1. Include the plan number "I-2008-021" in title block of each sheet.

2. Include Development Services Department PIA activity number "T08PI00019"on cover sheet.

3. Include sealed structural drawings for the proposed modified catch basin in this plan set.

4. Provide supporting hydraulic analysis and calculations for all the proposed drainage structures.

5. Provide details for the proposed catch basin and other improvements on Roasales Street and the proposed 36" storm drain, within the public rights-of-way, at the northwest corner of the project site.

6. Provide curb access ramps must be per PC/Cot Std. Dtl. 207. Proposed ramps are not per PC/COT standards.

Refer to redline plans for additional comments and comment details.

If you have any questions, I can be reached at 837-6647 or Richard.Leigh@tucsoz.gov
06/02/2008 JOSE ORTIZ DOT TRAFFIC REVIEW Denied June 2, 2008
ACTIVITY NUMBER: T08PI00019
PROJECT NAME: Fire Central
PROJECT ADDRESS: 300 S Fire Station Pl
PROJECT REVIEWER: Jose E. Ortiz PE, Traffic Engineer

Resubmittal Required: Traffic Engineering does not recommend approval of the PIA Plan; therefore a revised PIA Plan is required for re-submittal.

The following items must be revised or added to the plan.

1. Include a response letter with the next submittal that states how all comments have been addressed.

2. See redlines on the submitted drawings and address the additional redline comments. During the next submittal please re-submit the roll of redlines for back checking purposes.

3. Was a study conducted to warrant a crosswalk across Simpson Street? If no study was conducted then remove the proposed crosswalk from plan set.

4. Place the PIA and CDRC Case number on the cover sheet.



If you have any questions, I can be reached at 791-4259 x76730 or Jose.Ortiz@tucsonaz.gov
06/13/2008 LANCE PETERSON DOT STREET MAINTENANCE REVIEW Approved
06/16/2008 SMONTIE1 PIA COORDINATOR CUSTOMER CALLED Completed
06/16/2008 SMONTIE1 PIA COORDINATOR OUT TO CUSTOMER Completed