Plan Number: T08PI00015
Parcel: Unknown

Review Status: Completed

Review Details: PIA RESUBMITTAL

Plan Number - T08PI00015
Review Name: PIA RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/05/2008 SMONTIE1 UTILITY CLEARANCES COT STREETS DIVISION Denied Please submit utility clearance letters.
06/05/2008 SMONTIE1 UTILITY CLEARANCES COT WATER NEW DEVELOPMENT Denied Please submit utility clearance letters.
06/05/2008 SMONTIE1 UTILITY CLEARANCES PC WASTEWATER MGMT Denied Please submit utility clearance letters.
06/05/2008 SMONTIE1 UTILITY CLEARANCES QUEST COMMUNICATION Denied Please submit utility clearance letters.
06/05/2008 SMONTIE1 UTILITY CLEARANCES TUCSON ELECTRIC POWER CO Denied Please submit utility clearance letters.
06/05/2008 SMONTIE1 UTILITY CLEARANCES COX COMMUNICATION Denied Please submit utility clearance letters.
06/05/2008 SMONTIE1 UTILITY CLEARANCES SOUTHWEST GAS CORP Denied Please submit utility clearance letters.
06/05/2008 SMONTIE1 UTILITY CLEARANCES EL PASO NATURAL GAS Denied Please submit utility clearance letters.
06/05/2008 SMONTIE1 UTILITY CLEARANCES KINDER MORGAN ENERGY Denied Please submit utility clearance letters.
07/01/2008 RICHARD LEIGH DOT ENGINEERING REVIEW Denied July 1, 2008

SUBJECT: Lodge On The Desert, PIA T08PI0015. I-2008-015

PROJECT REVIEWER: Richard Leigh, DOT, Permits and Codes Section

RESUBMITTAL REQUIRED: Permits and Codes Section has reviewed the PIA Plan and does not recommend approval of the PIA Plan at this time. The following comments need to be addressed in the next submittal.

1. Sheet 2, Detail "D": Indicate the composition of the proposed sidewalk.

2. The existing curb access ramp on the northeast corner of Holmes Street and Alvernon Way will have to be brought into compliance with current ADA requirements.

3. Sheet 2, Detail "Scupper Plan": Provide details for the proposed scupper spillway.

Please refer to redline plans for additional comments and comment details.

If you have any questions, I can be reached at 837-6647 or Richard.Leigh@tucsoz.gov
07/03/2008 LANCE PETERSON DOT STREET MAINTENANCE REVIEW Approved
07/07/2008 JOSE ORTIZ DOT TRAFFIC REVIEW Approved
07/08/2008 SMONTIE1 PIA COORDINATOR CUSTOMER CALLED; PLANS @ AMBASSADOR Completed
07/08/2008 SMONTIE1 PIA COORDINATOR OUT TO CUSTOMER Completed