Review Date Reviewer's Name Type of Review Description Status Comments
03/20/2008 SMONTIE1 UTILITY CLEARANCES COT STREETS DIVISION Denied PLEASE SUBMIT UTILITY CLEARANCE LETTERS.
03/20/2008 SMONTIE1 UTILITY CLEARANCES COT WATER NEW DEVELOPMENT Denied PLEASE SUBMIT UTILITY CLEARANCE LETTERS.
03/20/2008 SMONTIE1 UTILITY CLEARANCES PC WASTEWATER MGMT Denied PLEASE SUBMIT UTILITY CLEARANCE LETTERS.
03/20/2008 SMONTIE1 UTILITY CLEARANCES QUEST COMMUNICATION Denied PLEASE SUBMIT UTILITY CLEARANCE LETTERS.
03/20/2008 SMONTIE1 UTILITY CLEARANCES TUCSON ELECTRIC POWER CO Denied PLEASE SUBMIT UTILITY CLEARANCE LETTERS.
03/20/2008 SMONTIE1 UTILITY CLEARANCES COX COMMUNICATION Denied PLEASE SUBMIT UTILITY CLEARANCE LETTERS.
03/20/2008 SMONTIE1 UTILITY CLEARANCES SOUTHWEST GAS CORP Denied PLEASE SUBMIT UTILITY CLEARANCE LETTERS.
03/20/2008 SMONTIE1 UTILITY CLEARANCES EL PASO NATURAL GAS Denied PLEASE SUBMIT UTILITY CLEARANCE LETTERS.
03/20/2008 SMONTIE1 UTILITY CLEARANCES KINDER MORGAN ENERGY Denied PLEASE SUBMIT UTILITY CLEARANCE LETTERS.
04/07/2008 LANCE PETERSON DOT STREET MAINTENANCE REVIEW Denied We have reviewed this plan and have the following comments:

1. Will there be any landscaping installed with this project? If so, please submit the landscape plan to Paul Rosenboom at 4004 S. Park Avenue for review.
2. It appears that the new pavement just matches the existing pavement cross-slope. Since there are no profiles with the plans, please make sure that there are no ponding areas in the pavement.
3. All work in the right of way needs to be coordinated with Paul Rosenboom at 791-5279 ext 234 to prevent damage to existing landscaping and irrigation.

No further comments.
04/21/2008 JOSE ORTIZ DOT TRAFFIC REVIEW Approv-Cond Call out for obliteration of existing striping along 22nd Street at Circulo Montana El Gato.

Place the PIA and Case number on the cover sheet.
04/21/2008 GARY WITTWER DOT LANDSCAPE REVIEW Denied 1. Please address the Native Plant Preservation Ordinance within the ROW.
2. You have included detail 207 - 4c of 5. Curb Access Ramp at a raised median. Where would this occur?
04/24/2008 SMONTIE1 PIA COORDINATOR CUSTOMER CALLED Completed
04/24/2008 RICHARD LEIGH DOT ENGINEERING REVIEW Denied April 23, 2008

SUBJECT: Starr Pass Vistas, Village 2, offsite, PIA T08PI0013, I-2008-017

PROJECT REVIEWER: Richard Leigh, DOT, Permits and Codes Section

RESUBMITTAL REQUIRED: Permits and Codes Section has reviewed the PIA Plan and does not recommend approval of the PIA Plan at this time. The following comments need to be addressed in the next submittal.

1. Include the plan number "I-2008-013" in title block of each sheet.

2. Include Development Services Department PIA activity number (T08000017) on cover sheet.

3. Include the subdivision's recordation information on cover sheet.

4. Approved tentative plat must be submitted with next review submittal.

5. Clearly label any roadway infrastructure which will be constructed under a different plan set.

6. Show and label all existing roadway infrastructures (curb, sidewalk, access ramps, etc). Use differing line weights for existing and proposed structures. Additionally, use symbols and abbreviations per PC/COT Standard. Details. 100 and 101 and include all linework used in plan set in the legend.

7. Provide a profile view for the proposed curb on 22nd Street and pavement widening on Greasewood Road (include edge of pavement stationing/offsets).

8. Label proposed curb access ramps and reference details.

9. Has a Development Standard Modification Request (DSMR) been requested for the omission of sidewalk between stations 21+69, LT and 23+49, LT ( 22nd Street). List any DSMR data as a general note.

10. Why is curb and sidewalk not being provided along the entire frontage of the subdivision per Development Standard 3-01.3.3?

11. Indicate the application of a thickened pavement edge for the pavement widening along Greaswood Road. Additionally, provide a thickened edge detail.

Refer to redline plans for additional comments and comment details.