Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T08OT02109
Parcel: 128010230

Review Status: Completed

Review Details: FLOODPLAIN

Permit Number - T08OT02109
Review Name: FLOODPLAIN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/25/2008 BIANCA RAMIREZ ENGINEERING REVIEW Denied DATE: August 25, 2008
SUBJECT: Floodplain Use Permit
TO: SBBL
LOCATION: 6100 E Broadway, T14S, R14E, Section 13, Ward 6
REVIEWERS: Bianca Ramirez, CFM
ACTIVITY: T08OT02109 (First Review)


RESUBMITTAL REQUIRED: Floodplain Use Permit

SUMMARY: Engineering Division of Development Services Department has received and reviewed the proposed floodplain use permit for the above referenced property. Engineering Division does not recommend approval of the floodplain use permit at this time. Please address the following review comments prior to the next submittal.

Floodplain Use Permit:

1. Identify on site plan which building is being demolished on plan.
2. Provide FEMA information on site plan include community number, FIRM panel, suffix and zone.
3. Indicate Base Flood Elevation = 2572.6' NGVD 1929 Regulatory Elevation = 2573.6 NGVD 1929. Complete conversion as needed from 88 Datum. Provide finished floor elevation of proposed building on plan.
4. Verify that plan represents what is actually on site. Aerial does not match what is depicted on plan provided.
5. Additional comments may be forthcoming.

If you have any questions, I can be reached at 837-4928 or Bianca.Ramirez@tucsonaz.gov

Bianca C. Ramirez
Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 837-4928 office
(520) 879-8010 fax

Final Status

Task End Date Reviewer's Name Type of Review Description
09/30/2008 SUE REEVES APPROVAL SHELF Completed
09/30/2008 DELMA ROBEY OUT TO CUSTOMER Completed