Permit Number: T08OT01830
Parcel: 99999999A

Review Status: Completed

Review Details: FLOODPLAIN

Permit Number - T08OT01830
Review Name: FLOODPLAIN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/14/2008 PAUL MACHADO ENGINEERING REVIEW Denied To: Bruce Paton, P.E. DATE: August 19, 2008
Rick Engineering Company,Inc.
1745 E. River Rd., Ste. 101
Tucson, Arizona 85718
SUBJECT: Houghton Town Center, Phase I
Grading Plan T08BU00493 (Second Review)
T15S, R15E, Section 26 and 35

RESUBMITTAL REQUIRED: Grading Plan, Drainage Report and SWPPP

The Grading Plan (GP), Drainage Report (DR) and Stormwater Pollution Prevention Plan cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Grading Plan:
1. The GP has been accepted by engineering.

Drainage report:
1. The DR has been accepted by engineering.

Stormwater pollution prevention plan:
1. The concrete washout area must be addressed under this permit. Revise the SWPPP to include the concrete washout area on these plans and re-submit.


If you have any questions, I can be reached at 837-4932 or Paul.Machado@tucsonaz.gov
Paul P. Machado
Senior Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 837-4932 office
(520) 879-8010 fax
C:/9044 S. Houghton Rd_GRAD 2

Final Status

Task End Date Reviewer's Name Type of Review Description
09/08/2008 DELMA ROBEY APPROVAL SHELF Completed
09/08/2008 DELMA ROBEY OUT TO CUSTOMER Completed
09/08/2008 GERARDO BONILLA REJECT SHELF Completed