Permit Review Detail
Review Status: Completed
Review Details: SITE
Permit Number - T08OT01763
Review Name: SITE
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/09/2008 | DAVE MANN | FIRE | REVIEW | Approved | |
| 09/09/2008 | TERRY STEVENS | ZONING | REVIEW | Denied | DSD TRANSMITTAL FROM: Terry Stevens Lead Planner PROJECT: T08OT01763 395 N. Silverbell Rd. Site Plan - Parking Lot Reconfiguration TRANSMITTAL DATE: 09/09/08 COMMENTS: Please resubmit revised drawings along with redlines and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed. 1. Provide a copy of the last approved site plan for the area located to the south of this project. (Building "C" and the parking lot located east of building "C") 2. Clarify the pedestrian circulation path from the southern most handicap parking spaces to the pedestrian circulation path to the buildings. The crosswalk indicated at the southwest corner of this project is incorrect, the existing southern handicap ramp may be required to be relocated. 3. Provide the location of the landscape border on page x1.1. 4. Provide the location of the existing and future right of way, existing and future curb location and sight visibility triangles on page x1.1. 5. The parking spaces along the east property line may be required to have wheel stops at each parking space in order to prevent overhanging the landscape border and or overhanging the property line. Clearly indicate the location of the wheel stops on the site plan. 6. Clearly indicate the location of the existing and proposed sidewalk located within the right of way along the east side of this project. 7. Clearly indicate the direction of travel for traffic at the northeast corner of this project at the 20' wide PAAL. If you have any questions about this transmittal, please call Terry Stevens, (520) 837-4961 C:\planning\cdrc\DSD\T08OT01763.doc |
| 09/11/2008 | RONALD BROWN | ZONING HC SITE | REVIEW | Denied | 12 SEPTEMBER 2008 T08OT01763/CARONDELET HEALTH NETWORK REVIEWED BY RON BROWN ACCESSIBLE REVIEW 2006 IBC/ICC 117.1 DENIED: SEE COMMENTS BELOW I. SHEET g0.1 A. DENOTE GOVERNING ACCESSIBILITY CODE; 2006 IBC/ICC 117.1 FOR PRIVATE PROPERTY. B. DENOTE RIGHT OF WAY ACCESSIBILITY STANDARDS; COT DOT STANDARDS. II. SHEET x0.1 C. PROVIDE AN ACCESSIBLE ROUTE CONNECTION, A NEW MARKED CROSSING, FROM THE PARTIALLY NEW AND EXISTING ACCESSIBLE PARKING SPACES TO THE ACCESSIBLE ROUTE IN FRONT OF THE "NEW MEDICAL FACILITY, 3 FLOORS". III. SHEET X1.1 D. PROPERTY LINE IS NOT SHOWN ON DRAWING. PROVIDE PROPERTY LINES. AS PER SHEET L2, WHERE PROPERTY LINES ARE SHOWN, IT APPEARS THAT ALL R.O.W. ENTRANCE DRIVES AND PARALLELING PEDESTRIAN WAYS ARE NOT IN THE R.O.W. AND ARE INSIDE THE PROPERTY LINE. THEREFORE ENTRANCE DRIVE, PEDESTRIAN WAYS, RAMPS AND CROSSINGS MUST BE IN COMPLIANCE WITH 2006 IBC/ICC 117.1. 1. CHANGE NOTE 4 TO READ "2006/ICC 117.1 ACCESSIBILITY STANDARDS". E. DETAIL 2: SHOW ACTUAL SITE PLAN PARKING DESIGN, GENERIC LAYOUTS ARE NOT ACCEPTABLE. SHOW PLANTER BOX AND PARKING SIGN LOCATIONS IN FRONT OF ALL LANDSCAPING. F. DETAIL 4: PROVIDE A MINIMUM OF 3' CLEAR BEHIND DETECTABLE WARNING. G. DETAIL 1 - SITE PLAN: 1. INSURE THAT ALL PAINTED STRIPES FOR THE MARKED CROSSINGS ARE THE SAME WIDTH AS THE RAMP ENTRANCES AND EXITS AND ARE A MINIMUM OF 3' WIDE 2. .PROVIDE A 6" HIGH SURFACE MOUNTED CURB IN FRONT OF ALL ACCESSIBLE PARKING SPACES TO PROVIDE A SEPARATION FROM THE ACCESSIBLE ROUTE AND THE ASPHALTIC PAVING. TAPPER CURB DOWN AT THE ACCESS AISLES. REFERENCE MARKED UP DETAIL A-A/C100. REFERENCE ZONING COMMENTS FOR ADDITION INFORMATION FOR SEPARATION 3. ALL CURB AND SIDEWALK RAMPS ARE TO COMPLY WITH 29006 IBC/ICC 117.1, SECTIONS 405 AND 406. PROVIDE LARGE SCALE DETAILS OF ALL DIFFERENT TYPES OF RAMPS DESIGNED AND REQUIRED. SHOW SIZE, DIMENSIONS, SLOPES, FINISHES, ACCESSIBLE ROUTE, DETECTABLE WARNINGS AND ETC. 4. 5 "VAN ACCESSIBLE" SPACES ARE REQUIRED. PLEASE IDENTIFY THE "VAN ACCESSIBLE" SPACES. 5. THE MARKED CROSSING LOCATED AT THE SOUTH WEST CORNER OF THE SIDE DOERS NOT WORK AT THE TRANSITION TO THE SOUTHERLY MOST CURB RAMP; TOO STEEP AN ENTRANCE ANGLE. MAYBE RELOCATE THE CROSSING TO THE WEST TO ACQUIRE A MORE DIRECT ACCESS. 6. PROVIDE AN ACCESSIBLE ROUTE CONNECTION, A NEW MARKED CROSSING, FROM THE PARTIALLY NEW AND EXISTING ACCESSIBLE PARKING SPACES TO THE ACCESSIBLE ROUTE IN FRONT OF THE "NEW MEDICAL FACILITY, 3 FLOORS". 7. VERIFY ACCESSIBILITY TO ALL BUILDING ENTRANCES AS REQUIRED PER 2006 IBC SECTION 1105 AND ICC 117.1, SECTIONS 302 AND 303. IV. SHEET C100 H. SECTION A-A: .PROVIDE A 6" HIGH SURFACE MOUNTED CURB IN FRONT OF ALL ACCESSIBLE PARKING SPACES TO PROVIDE A SEPARATION FROM THE ACCESSIBLE ROUTE AND THE ASPHALTIC PAVING. TAPPER CURB DOWN AT THE ACCESS AISLES. I. SITE LAYOUT: SHOW LOCATIONS OF ACCESSIBLE SIGNS IN FRONT OF ALL LANDSCAPING. V. SHEET C402 J. ALL 207 DETAILS ARE FOR R.O.W. DEVELOPMENT ONLY, NOT IN THIS PROJECT. END OF REVIEW |
| 09/18/2008 | PETER MCLAUGHLIN | LANDSCAPE | REVIEW | Denied | 1. Revise street landscape border information, including street name (the project does not front on Escalante Road) and landscape border dimension in the table/calculations on sheet L-2. 2. Revise the three planter islands in the middle of the parking lot which are centered on the vehicle parking spaces to be located as the others are, so that the trees are planted at the intersections of the parking lot stripes rather than in between them. This will allow for a longer vehicle overhang dimension in these spaces and avoid damage to tree trunks and to vehicles. DS 2-06.3.3.E (For clarity refer to the diagram towards the end of DS 2-06 for a depiction of the requirement of DS 2-06.3.3.E) 3. Where proposed within the sight visibility triangles revise Justicia californica (Chuperosa), which can grow to 5 or 6 feet in height, to be another type of shrub suitable for planting within the SVT. DS 2-06.3.8.G; DS 3-01.5.1.A.1 4. As part of Iandscape notes on sheet L-2, include a statement that d.g. shall also be used within the right-of-way area between the curb and sidewalk. LUC 3.7.2.4.A.4 5. In the drawing on sheets L-2 and L-3 a symbol, which looks like a sun, appears within a parking sapce located in the eastern portion of the parking lot. This symbol is not found in the landscape legend or irrigation legend. Please clarify or remove symbol. |
| 09/19/2008 | PETER MCLAUGHLIN | NPPO | REVIEW | Approved | |
| 10/01/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 10/06/2008 | ELIZABETH EBERBACH | ENGINEERING | REVIEW | Approved | PARKING REGRADING. SEE PERMIT CONDITIONS - EE |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/08/2008 | CPIERCE1 | OUT TO CUSTOMER | Completed |
| 10/08/2008 | CPIERCE1 | REJECT SHELF | Completed |