Permit Number: T08OT01173
Parcel: 11519027A

Address:
1701 W GRANT RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T08OT01173
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/09/2008 ELIZABETH EBERBACH ENGINEERING REVIEW Denied TO: Pete Salonga, PE
REVIEWER: Elizabeth Eberbach, PE
ACTIVITY NUMBER: T08OT01173
SUBJECT: 1701 W Grant Rd 2nd Floodplain Plan Review
LOCATION: T14S R13E Sec3, Lots 18, 19, 20, 25, and 26 of Grant - Dragoon Industrial Park
WARD: 1

SUMMARY: The west portion of the parcel lies partially within the Grant Auto Care Center Development Plan and within lots 18, 19, 20, 25, and 26 of Grant - Dragoon Industrial Park. Engineering Division of Development Services Department has received and reviewed the plan 2nd re-submittal of the floodplain use permit package and does not recommend approval of the floodplain use permit application until the remaining comment is addressed.

SITE AND GRADING PLAN REVIEW COMMENTS:
1) DS Sec.11-01.4.1.C.4: Provide a detail showing how west drainage swale will be constructed to convey flows from the north equipment display area to assure equipment display area will drain positively, and to assure that this swale directs stormwater toward front of project and away from parcel at 1790 W Sahuaro Dr. Clarify detail section C-C on sheet 2 for the Sections and Details sheet.

For resubmittal provide 2 copies revised drainage report, Floodplain Use Permit Application and a response letter. If you have any questions, I can be reached at 837-4934.

Elizabeth Eberbach, PE
Civil Engineer
Engineering Division
Development Services