Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T08OT01173
Parcel: 11519027A

Address:
1701 W GRANT RD

Review Status: Completed

Review Details: FLOODPLAIN

Permit Number - T08OT01173
Review Name: FLOODPLAIN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/10/2008 ELIZABETH EBERBACH ENGINEERING REVIEW Denied TO: Pete Salonga, PE
REVIEWER: Elizabeth Eberbach, PE
ACTIVITY NUMBER: T07CM00963, T08BU00922, T08OT01173
SUBJECT: 1701 W Grant Rd 2nd submittal Site/Grading/Floodplain Plan Review
LOCATION: T14S R13E Sec3, Lots 18, 19, 20, 25, and 26 of Grant - Dragoon Industrial Park
WARD: 1

SUMMARY: The west portion of the parcel lies partially within the Grant Auto Care Center Development Plan and within lots 18, 19, 20, 25, and 26 of Grant - Dragoon Industrial Park. Engineering Division of Development Services Department has received and reviewed the plan 2nd re-submittal of the site plan and does not recommend approval of the site plan, grading plan, and floodplain use permit application until the following comments are addressed.

SITE AND GRADING PLAN REVIEW COMMENTS:
1) Tucson Code 26-8(b)(1): Explain in the drainage report which type of Zone X-shaded is applicable to this site and provide discussion of the impact to the project given location of the project within the X-Shaded zone region.
2) DS Sec.2-02.2.1.A.32: Provide dimensions for refuse container interior on detail or planview to clarify minimum inside clear dimension of 10 feet by 20 feet between bollards that are required between containers and enclosure's rear and sidewall.
3) DS Sec.11-01.4.1.C.4: Provide a detail showing how west drainage swale will be constructed to convey flows from the north equipment display area to assure equipment display area will drain positively, and to assure that this swale directs stormwater toward front of project and away from parcel at 1790 W Sahuaro Dr. Clarify detail section C-C on sheet 2 for the Sections and Details sheet.
4) DS Sec.11-01.16: Add note that a special inspection is required for the passive methane vent well system. Also, prior to final inspection, provide geologist's field reports regarding inspection during construction and after construction of the methane systems.
5) Tucson Code Sec.26-23: Provide a SWPP plan/report for this project as none was found in the submittal package. Call to discuss items needed for the completion of the SWPPP.

For resubmittal provide three copies of the revised Site Plan sheets, three copies of the Grading Plan sheets, 2 copies revised drainage report, one copy of the Landfill Methane Development Plan report, Floodplain Use Permit Application, Grading Permit Application, 3 copies of the SWPPP plans, and a response letter. If you have any questions, I can be reached at 837-4934.

Elizabeth Eberbach, PE
Civil Engineer
Engineering Division
Development Services

Final Status

Task End Date Reviewer's Name Type of Review Description
07/11/2008 CPIERCE1 OUT TO CUSTOMER Completed